I. General
Characteristics
Interlocks
Additional Safety Interlocks
II. Electric Parameters
Items |
units |
parameters |
Rated voltage |
kV |
40.5 |
Rated frequency |
Hz |
50 |
Rated short-time power frequency withstand voltage 1 min (interphase, to ground and between breaks) |
kV |
95 (118) |
Rated lightning impulse withstand voltage (interphase, to ground and between breaks) |
kV |
190 (215) |
Rated short-circuit breaking current |
kA |
25, 31.5 |
Rated short-time withstand current, 4s |
kA |
25, 31.5 |
Rated short-circuit closing current |
kA |
63, 80 |
Rated peak withstand current |
kA |
63, 80 |
Rated bus current |
A |
1250,2500,3150 |
Feeder current |
A |
1250, 2500 |
III. Overall Dimensions
Items |
Unit |
Parameters |
Width |
mm |
1200/14001 |
Height |
mm |
2800/30102 |
Depth |
mm |
2650/34503 |
Weight |
kg |
1800~2300 |
IV. Low Voltage Compartment Dimensions
Items |
Unit |
Parameters |
- |
- |
Standard type |
Width |
mm |
1200/14001 |
Height |
mm |
705 |
Depth |
mm |
450 |
V. Cable Compartment Dimensions
Items |
Units |
Parameters |
Width |
mm |
1200/14001 |
Height |
mm |
1280 |
Cable terminal above ground |
mm |
≥750 |
1. Cabinets used in substation
2. Switch cabinet with absorption device
3. Switch cabinet with back cabinet
1. Low voltage compartment door lock
2. Manual energy storage operational hole
3. High voltage compartment door lock
4. Handle for opening high-voltage compartment door
5. Observation hole of circuit breaker closing/opening status, energy storage, and counter
6. Observation hole of handcart working/testing position status indication
7. Circuit breaker closing button
8. Circuit breaker opening button
9. Mechanical position indication and operational of grounding switch
10. Chassis in/out operational hole
11. Pressure relief channel
12. Bus
13. Circuit breaker
14. Chassis
15. Grounding switch
16. Connecting cable
17. Current transformer
18. Static contact
19. Moving contact
20. Contact box