I. Structure
All-weather, Strong Adaptability to Harsh Environments:
Ø 24 hour water-immersion test under 12KV power demonstrates that the protection level IP68 can reliably withstand summer flooding.
Ø Fully sealed, Fully Insulated, Maintenance-free.
Ø All the high-voltage energized parts are sealed in main cabinet which can’t be reached.
Ø Personal safety:Reliable pressure relief channel, arc-fault resistance, passed 20KA inner-arcing type test.
Ø Three switch positions achieve natural interlock. Switch position indications are clear and reliable, equipped with powered indication.
Ø Modular Design, Configuration Flexibility.
Ø We can adopt multi units in one box, or separation type of free combination of various modules, to meet different customer needs.
II. Technical Parameters
Items |
Unit |
Load switch |
Fuse combination |
Vacuum circuit breaker |
|
Rated voltage |
kV |
12 |
12 |
12 |
|
Rated current |
A |
630 |
125* |
630 |
|
Power frequency withstand voltage (1min) |
Interphase, to ground, between breaks |
kV |
42 |
42 |
42 |
48 |
48 |
48 |
|||
Lightning impulse withstand voltage (BIL) |
Interphase, to ground, between breaks |
kV |
75 |
75 |
75 |
85 |
85 |
85 |
|||
Zero indication (1min) power frequency withstand voltage |
kV |
32 |
32 |
32 |
|
Secondary loop power frequency withstand voltage (1min) |
V |
2000 |
2000 |
2000 |
|
Rated load breaking current |
A |
630 |
630 |
630 |
|
Rated charging breaking current |
A |
10 |
10 |
25 |
|
Rated short circuit breaking current |
kA |
\ |
31.5* |
20 |
|
Rated transfer breaking current |
A |
\ |
1700 |
\ |
|
Rated short circuit closed current (peak) |
kA/time |
50/5 |
\ |
50 |
|
Grounding switch closed current (peak) |
kA/time |
50/2 |
\ |
50/2 |
|
Rated short-time withstand current |
kA/s |
20/4 |
20/4 |
20/3 |
|
Rated peak withstand current |
kA |
50 |
50 |
50 |
|
Mechanical life |
time |
5000 |
5000 |
10000 |
|
SF6 air rated pressure (20℃) |
MPa |
0.03 |
0.03 |
0.03 |
|
SF6 air annul leakage rate |
% |
<0.05 |
<0.05 |
<0.05 |
Note: Item marked with * means that the data depends on high-voltage fuse.