I. General
Characteristics
Ø Mechanical dynamic position indicator.
Ø The closing/opening status of disconnecting switch and grounding switch can be indicated respectively on mechanical dynamic position indicator.
Ø Operating handle socket and control elements are obviously set adjacent to closing/opening indicator of controlled switches.
Ø All the switch operations can be carried out only when high-voltage compartment door closed.
Ø All the parts and components installation heights meet the requirements of human engineering.
Ø Options: Capacitive electric indicator can be used to detect feeder or power of busbar.
Interlocks
Ø Interlock meets GB3906 and IEC 62271-200 standards
Ø Feeder grounding switch can only be operated when main switch on test position.
Ø The switch device can be removed only when main switch opened and grounding switch disconnected.
Ø Main switch can be operated only at test, working and removed position.
Ø The operations can be only carried out when high-voltage compartment door closed.
Additional Safety Interlocks
Ø Mechanical coding can avoid low current switch pugging in high current switchgear by mistake.
Ø Reliable mechanical interlock connects high-voltage compartment door and removable part.
Ø Options: Electromagnetic interlock, padlock.
Ø Mechanical padlock can be set at handcart inlet and grounding switch operation hole to avoid misoperation.
II. Overall Dimensions
Category |
Items |
Parameters |
Width |
Circuit breaker cabinet |
- |
≤630A |
650 |
|
1250A~2500A |
800 |
|
3150A~4000A |
1000 |
|
Disconnecting handcart cabinet |
- |
|
≤2500A |
800 |
|
3150A |
1000 |
|
Transformer used in substation |
1000 |
|
Bus segment cabinet |
- |
|
≤2500A |
2×800 |
|
3150A |
2×1000 |
|
Measuring cabinet |
800,1000 |
|
Lifting cabinet |
800,1000 |
|
Contactor cabinet |
650 |
|
Height mm |
≤31.5KA |
2200 |
40 kA |
2300 |
|
Switchgear used in substation |
2500 |
|
Contactor cabinet |
2200 |
|
Depth mm |
Assembled with ordinary circuit breaker |
- |
≤31.5 kA and bus current≤2500A |
1350 |
|
≤31.5 kA and bus current≥3150A |
1450 |
|
40 kA |
1450 |
|
assembled with solid-closure circuit breaker |
- |
|
≤31.5 kA and bus current≤2500A |
1350 |
|
≤31.5 kA and bus current≥3150A |
1500 |
|
40 kA |
1500 |
|
Contactor cabinet |
1350,1500 |
|
Weight kg |
1250A/31.5 kA standard cabinet |
±850kg |
3150A/40 kA standard cabinet |
±1300kg |
Notes:
1) The rated current of switchgear under forced air cooling is up to 4000A;
2) H1: the height from standard low-voltage compartment top to the ground is 2075mm;
H2: the height from raising low-voltage compartment top to the ground is 2350mm;
3) Upper outgoing, or bus accessories, bus current ≤ 2500A,cabinet deepens 130mm;
Upper outgoing, or bus accessories, bus current>2500A,cabinet deepens 200mm;
Backpack plans, rated current ≤2000A, the depth is 460mm;
Backpack plans rated current >2000A, the depth is 620mm
III. Cabinet Structure
40A, rated current 4000A, assembled with ordinary circuit breaker.
25kA/31.5kA, rated current≤2500A, assembled with ordinary circuit breaker≤40kA, rated current≤4000A, assembled with solid-closure circuit breaker.

1. Low-voltage Compartment Door
2. Relay Protection Device
3. High-voltage Compartment Door
4. High-voltage Compartment Door Lock
5. Analog Circuit Diagram
6. Circuit Breaker “open/close” Button and Energy Storage Spring Hole
7. Observation Window
8. High-voltage Compartment Door Opening Handle
9. Operational Handle for Moving Switch Device
10. Mechanical Position Indication and Operation Handle Hole of Grounding Switch
11. Pressure Relief Channel
12.Bus
13. Insulator with Bushing
13’. Contact Box
14. Bushing Current Transformer
14’. Current Transformer
15. Four Cables Connection for Each Phase
16. High Speed Grounding Switch
17. Low-voltage Plug/Socket
18. Circuit Breaker Operating Mechanism and Interlock Device
19. Vacuum Arc Extinguishing Chamber
20. Moving/static contact
21. CB and grounding operating mechanism and interlock device
A . High-voltage Compartment
B. Bus Compartment
C. Cable Compartment
D. Removable Circuit Breaker
E. Low-voltage Compartment