I. General
The frames of MNS series are highly flexible. There is no need of repair after installation. Different standard components can be installed in the gears to meet various kinds of applicable requirements. Because combined design is used in the entire systems including electric appliance structure, this optimized design can meet different components’ demands and adapt to different working environment, to reach corresponding protection level.
Both the design and material of MNS system can minimize the danger of fault arc occurrence. Once it occurs, it can be extinguished in time.
MNS system meets the requirements of Appendix AA in IEC298, it is proved through the fault arc measurement by an independent testing organization, as well as the type test, during the test, there is no effect on adjacent extracting type components after fault arc occurrence. After arc extinction, drawer-type components still can be operated after cleaning up. There is no change in the switchgears for the components with mechanical interlocks, even on the isolation position, there is no fault arc marks on switchgears surface.
There is no CFC or halogen contained in plastic material used in MNS system, this kind of plastic material has a flame-retardant and self-extinguishing characteristics. Compare with traditional product, the innovative MNS system has more advantages.
II. Technical Parameters
Rated Voltage |
Rated Current |
||
Rated Insulation Voltage U1 |
1000V three-phase AC, 1500V DC |
Bus |
\ |
Rated Operational Voltage U2 |
690V three-phase AC, 750V DC |
Rated Current |
To 5500A |
Rated Impulse Withstand Voltage U imp |
8KV |
Rated Peak Withstand Current |
To 250KA |
\ |
\ |
Rated Short-time Withstand Current |
\ |
Rated Voltage |
Rated Current |
||
\ |
\ |
Brunch Bus |
\ |
Overvoltage Level |
III |
Rated Current |
To 1200A |
Pollution Level |
3 |
Rated Peak Withstand Current |
To 110KA |
Rated Frequency |
50-60Hz |
Rated Short-time Withstand Current |
To 50KA |