I. General
It is applicable to all the low-voltage systems which need high reliability: power distribution and motor control systems.
The switchgears with modularized structure meet local standards, customs and requirements.
A. Blokset, modularized multi-functional system.
Multi-functional series:
Ø D type: power distribution cabinets below 6300A
Ø Dc type: power factor compensation cabinet
Ø Mf type: fixed motor control center
Ø Mx type: drawer style cabinet below 6300A
Ø Mw type: drawer style cabinet below 6300A
Ø Ms type: frequency converter and modularized system
Ø Standardized components
Ø Rapid manufacturing
Ø Functional design is easy to change
Ø Reasonable dimensions and internal configuration
Ø Take less area
Ø Simple main and auxiliary circuit connection
Ø Easy installation and less update cost
B. Blokset, reliable system without malfunction can ensure the high reliability and safety and enhance the protection on person and equipment.
Blokset provides all the guarantees:
Ø Blokset meets international standards, especially IEC60439-1, IEC60529 and IEC60947
Ø Blokset meets local standards, regulations and technical requirements.
Ø Schneider electrical switches are used for optimal operation.
C. Blokset, consistent, high-performance, economical Blokset modularized design can make reasonable installation cost. High quality and reliability ensure continuous power supply and durable systems.
Blokset is a kind of product with consistent plan:
Ø Accurate response to each technical specification.
Ø Easy installation, optimized dimension and connection.
Ø Guarantee purchase and installation time.
Ø Update and improvement costs controllable.
Ø Standardization and system upgradability make the maintenance costs controllable.
D. Blokset, professional manufacturer guarantees that that the quality and reliability of Blokset are established on the basis of the close cooperation with local specialists.
Besides the technical highlights, Schneider Electric will actively involve in all your projects to help you to success.
These businesses includes:
Ø Make a rapid respond to quotation and biddining.
Ø Design a solution plan with outstanding performance.
E. Blokset, Schneider Electric can guarantee their products quality and technical advantages with the key technologies in the field of switchgears and switches design and manufacturing.
Ø Shorten the delivery and installation time because of standardized component configuration.
Ø Innovated design which is consistent with other Schneider electrical solutions plays a role in helping each projects to success.
Ø Schneider experts work in close cooperation with customers guarantee the rapid response to customers’ installation requirements and effective service.
II. Main Technical Indicators
Blokset switchgear is composed of four different compartments, they are:
1. Bus compartment
2. Component compartment
3. Outgoing cable compartment
4. Accessory compartment
Three depths and six widths
Blokset series can form various switchgears with different depths and widths through the combination of basic frames and extended frames
There are three depths for basic frame:
1. 400mm
2. 600mm
3. 1000mm
4. Form by basic frame with 400mm and 600mm in depths
There are six depths for basic frame:
1. 500mm (Mv type)
2. 600mm (Mx type)
3. 700mm
4. 900mm (Mw type)
5. 1200mm (apply to masterpactMT40b/50/63)
Extended cabinets can be installed to the both sides of the basic cabinet which is 700mm in width. (200mm or 400mm)
III. Technical Parameters
Standards |
||
Type Test |
IEC60439/VDE0660part500,DIN41-488/BS5486/EN60439-1 GB7251.12-2013 |
|
Earthquake Resistance |
Uniform building code California building code |
|
Internal Arc Resistance |
AS3439/1 |
|
Electrical Characteristics |
||
Rated Insulation Voltage |
1000VAC |
|
Rated Operating Voltage |
400/690VAC |
|
Rated Impulse Withstand Voltage |
12kv |
|
Overvoltage Type |
lv |
|
Pollution Level |
3 |
|
Frequency |
400Hz |
|
Rated Current |
||
Main Busbar |
Single busbar |
Double busbar |
Rated Current |
Below 4000A |
Below 6300A(1) |
Rated Peak Withstand Current |
63,105 or 187kA |
220kA |
Rated Short -time Withstand Current |
30,50 or 85kArms/1s |
100kArms/1s |
Surface Protection |
||
Outer Surface Protection |
Epoxy powder high-temperature polymer |
|
Standard Color |
RAL9002 (beige grey)/RAL7016 (black grey) |