KYN28-12(GZSI-12Z)Middle-mounted Switchgear Cabinet - - PRODUCTS - Shaanxi XD HI-TECH Medium-low Voltage Apparatus Co., Ltd
西电高科官网首页
  • 中文
  • English
Tel: +86-29-88248590
Fax: +86-29-88248591
PRODUCTS
Position:Home » PRODUCTS » KYN28-12(GZSI-12Z)Middle-mounted Switchgear Cabinet
KYN28-12(GZSI-12Z)Middle-mounted Switchgear Cabinet

I.General

KYN28-12 armoured middle-mounted metal enclosed switchgear (hereinafter referred to as switchgear) is our new designed and developed product on the basis of absorbing advanced technology abroad, which can replace the old metal enclosed switchgears, such as KYN1-10, JYN2-10, GBC-10 series, etc.

The shell whose mechanical strength is high is assembled when coated Al-Zn steel plates are processed, bended and molded by CNC machine tool so that tidy and beautiful product is ensured. The door is plastic sprayed coating therefore, it has the high impact resistance and corrosion resistance ability. The protection grade of shell is IP4X.
The main switch can be configured with VD4-type vacuum circuit breaker produced by ABB, Schneider HVX, C3 series fixed load switch, meanwhile, it also can be assembled with several domestic vacuum circuit breakers (such as VS1, VH1, VK, ZN28) to replace the similar domestic products.


II.Model Definition


III.Operational Environment

a. Ambient Temperature: -10℃~+40℃

b. Relative Humidity: Daily average is not greater than 95%, monthly average is not greater than 90%
c. Elevation: Not higher than 1000m
d. The seismic intensity should not be greater than 8-magnitude.
e. It should be operated in the place without danger of fire, explosion, serious dirtiness, chemical corrosion and acute shaking.
If it is planed to operate in the condition out of the above limits, the customers should negotiate with us to decide the allowable operational conditions and technical measures.


IV. Technical Parameters

Item

Unit

Parameters

Rated voltage

kV

3, 6, 7.2,12

Rated frequency

Hz

50

CB rated current

A

630, 1250, 1600, 2000,2500, 3150

Switchgear rated current

A

630, 1250, 1600, 2000,2500, 3150

Short-time withstand current

kA

20, 25, 31.5, 40, 50

Rated dynamic stability current(peak)

kA

50, 63, 80, 100, 125

Rated short circuit breaking current

kA

20, 25, 31.5, 40, 50

Rated short circuit closed current

kA

50, 63, 80, 100, 125

 

 

Rated insulation grade

1min power frequency withstand

voltage

kV

24, 3, 42

 

Lightning impulse

withstand voltage

kV

40, 60, 75

Protection level

Shell: IP4X.

When Isolation chamber and CB chamber door is open: IP2X.


V. Schematic Diagram


A. Busbar chamber

B. CB Handcart chamber

C. Cable chamber

D. Relay instrument chamber

 

1. Cabinet

2. Branch bar

3. Busbar

4. Isolated contacts

5. Contact box

6. Earthing switch

7. CT(Current transformer)

8. Zinc Oxide arrestor

9. Baseplate

10. Main grounding bar

11. Control line slot

12. Cable seal terminal

13. Grounding switch operating mechanism

14. Detachable horizontal clapboard

15. Wire rod mechanism

16. VCB (Vacuum Circuit Breaker)

17. Secondary Plug

18. Terminal board

19. Shutter

20. Detachable clapboard

21. Pressure release


VI. Installation Dimensions

Application of Switchgear

Width(W)

Depth(D)

Wire in and out at Bottom

Depth(D)

Wire in and out at Top

Zn63 / VS1

800

 

1500(1550)

 

 

 

1660

 

 

CB

 

1000

 

3AH,ZN12

800

 

1500(1550)

 

 

1660

 

CB

1000

VD4,VS1

800

 

1500(1550)

 

 

1660

 

CB

1000


Application of Switchgear

Width(W)

Depth(D)

Wire in and out at Bottom

Depth(D)

Wire in and out at Top

W-VAC

700

 

1660

 

 

 

1660

 

 

CB

 

800

 

VCP-W

800

 

1660

 

 

1660

 

CB

1000




Scan the qr code

Pay attention to our

CopyRight @xdhi-t.com 2014 All Right Shaanxi XD HI-TECH Medium-low Voltage Apparatus Co., Ltd
Company address: No. 2 Road Xi'an Weiyang West Ham District East Metro Symphony No. 6 Peace Industrial Park
Headquarters phone: 029-88248590/88890097 Fax: 029-88248591 postal code: 710086