I. General
UniGear ZS3.2 switchgear is composed of cabinet and circuit breaker equipped with removable parts, the cabinet divides into four compartments, circuit-breaker compartment, bus compartment, cable compartment and low-voltage compartment.
Bus Compartment
“D” type or rectangle main bus runs through the adjacent cabinets and is supported by branch bus, metal division plate and bus bushing. Supporting insulator isn’t needed in bus compartment. Insulation cover should be used at the connection of main bus and branch bus. Heat-shrinkable insulation bushing are applied for main bus and branch bus to form reliable compound insulation. Cabinets are separated by busbar bushing and division plate.
Cable Compartment
Current transformer, grounding switch, lightning arrester can be installed in the compartment. Spare space allows multi - cables connection.
Low-voltage Compartment
Various secondary components can be installed according to different control and protection requirements.
The secondary slot is wide enough, which is protected and shielded by metal plate.
Circuit Breaker
The guide rail is installed in the compartment for circuit breaker handcart movement between working position and isolation position and testing position, the valve shields static contact automatically after handcart is out.All the operations can be carried out when the door is closed.
Removable Part
Removable part is composed of frame and circuit breaker or other components. High-quality and reliable VD4 vacuum circuit breaker and HD4 SF6 circuit breaker can be chosen, removable parts with same parameters can be exchanged.
Anti- misoperation Interlock
A series of reliable interlocks are set to avoid misoperation and ensure personal and equipment safety.
II. Technical Parameters
Items |
Units |
Data |
Rated voltage |
kV |
40.5 |
Rated power frequency withstand voltage (1 min) |
kV |
95/118 (isolating break) |
Rated lightning impulse withstand voltage (full wave) |
kV |
185/215 (isolating break) |
Rated frequency |
Hz |
50/60 |
Main bus rated current |
A |
1600,2000,2500,3150 |
Branch bus rated current |
A |
1250,1600,2000,2500,3150* |
Circuit breaker rated current |
A |
1250,1600,2000,2500,3150* |
Circuit breaker rated short-circuit breaking current |
kA |
25,31.5 |
Rated peak withstand current |
kA |
63,80 |
Rated short-time withstand current (4s) (effective value) |
kA |
25,31.5 |
Auxiliary power voltage |
V |
DC110,220 |
Enclosure protection grade |
- |
IP4X |
Protection grade with circuit breaker compartment door open |
- |
IP2X |
Dimensions (W×D×H) |
mm |
1200×2565×2400 |
weigh |
kg |
1100~2000 |
III. Cabinet Structure
1. Shutter
2. Circuit breaker
3. Secondary plug
4. Main bus
5. Bus bushing
6. Grounding switch
7. Static contact box
8. Supporting insulator (electrical display device can be chosen)
9. Insulation division plate
10. Power cable
11. Plate heater
12. Current transformer
13. Pressure relief plate
14. Division plate