Project Information
Xi’an Triangle Aviation Technology co., Ltd (hereinafter referred to as “Triangle Aviation”) is co-founded by Shaanxi Provincial Government, Xi’an Municipal Government, Xi’an Yanliang National Aviation Hi-tech Industrial base, Shaanxi Hongyuan Aviation Forging co., Ltd and Xi’an Sansen investment co., Ltd.
Triangle Aviation has built a 400MN aviation forging hydraulic press and a forging product line. The total investment of this project is 784 million yuan, and come into use at the latter half of 2012. This project is National “Eleventh Five-Year Technology Support Program”, as well as Shaanxi Key Construction Project of National Aviation Hi-tech Industrial Base. We, Shaanxi XDHI-T Medium and low Voltage Apparatus co., Ltd, support them with 10KV HV control cabinet (S1 electric chamber), DC panel (S11, S12 electric chamber), and DC panel (S1 electric chamber).
Customers' Requirements
10KV HV control cabinet (S1 electric chamber), DC panel (S11, S12 electric chamber), and DC panel (S1 electric chamber). Customers has technical requirements about the 10KV metal-enclosed switchgear on functional design, structure, installation and experiment, thus all our product have meet the National Standard, Industrial Standard, environmental requirement and electric requirement.
Solutions
SN |
Parameter |
CB cabinet |
|
1 |
Cabinet types |
KYN |
|
2 |
Ur(KV)/Um |
10/12 |
|
3 |
Rated Frequency (Hz) |
50 |
|
4 |
Ir |
|
|
a)Main busbar rated current(A) |
3150 |
||
b)Main busbar thermal stable current (effective value) |
40kA 4s |
||
c)Main busbar dynamic stable current (peak) |
125kA |
||
d) Each circuit breaking short-circuit current periodic component (effective value) Short circuit current non-periodic component percentile when breaking |
40kA ≥40% |
||
5 |
Operating voltage |
DC220V |
|
6 |
Benchmark insulation level |
|
|
a)Impulse withstand voltage (kV) |
≥60 |
||
b)1min power frequency withstand voltage |
≥30 |
||
7 |
Grounding busbar rated current(A) |
|
|
8 |
Gross weight (kg) |
≤12000kg |
|
9 |
Dimensions (W×D×H)mm |
800*1500*2300 1000*15000*2300 |
|
10 |
Protection level |
IP4X |
Industrial Standards
GB3906-2006 Alternating-current metal-enclosed switchgear and control switch for rated voltages above 3.6 kV and up to and including 40.5 kV.
GB3309-89 Mechanical test at ambient temperature for high-voltage switchgear.
GB1984-89 High-voltage alternating-current circuit-breakers.
GB11022-1999 Common specifications for high-voltage switchgear and control switch standards.
GB311.1 Insulation Coordination of High Voltage (HV) Power Transmission and Transformation Equipment.
GB763 Heating of A.C. high-voltage apparatus under long runs.
(GB standards are equivalent to IEC standards)
Operational Conditions
Extreme maximum temperature: 42.2℃
Extreme minimum temperature-16.7℃
Mean annual temperature:13.4℃
Parameters
Nominal voltage: 10kV
Voltage fluctuation: ±5%
Power supply frequency: 50H
Power supply wiring: 3-phase 3-wire system, the system neutral point is an arc suppression coil grounding system.